PETROM EP Standard for Voltage and Earthing System
Onshore & Offshore.
Foreword
Scope
Range of applicability
Reference normative
General Assignations
Existent Voltage Levels
Recommended Voltages for New Projects
500 V, IT System
Requirements for Hazardous Areas
400/230 V, TNS System
400/230 V, TT System
400 V & 230 V, IT System, Offshore
6 kV, IT System
The present standard has been developed having regards of the following:
Limits of international standardization
Complexity and, in some case, unusual existent voltage levels in PETROM E&P;
Various lessons learnt: equipment bought at inaccurate voltage level, which fail very fast or require additional devices, e.g. transformer.
The standard is intending to present the existing level of voltage used in PETROM E&P and recommendations for the new developments.
Voltages for special appliance are out of scope of this procedure:
100V (110V) used in automation and instruments / measurement & electrical protection;
660V level, used in drilling activity as intermediary voltage
DC voltage.
The voltages presented below are providing through Romanian National Grid (onshore).
The standard applies to
PETROM E&P, Onshore & Offshore, for the plants inside
Abroad the standard may be advisory only
SR EN 61140:2002 Protection against electric shock - Common aspects for installation and equipment
SR EN 60 Safety of machinery - Electrical equipment of machines -- Part 1: General requirements
SR EN Marking of electrical equipment with ratings related to electrical supply. Safety requirements
SR HD 472 S1:2002 Nominal voltages for low-voltage public electricity supply systems
HD 384.3 S2:2004 Electrical installations of buildings. Part 3: Assessment of general characteristics
HD 60364-4-41:2007 Low-voltage electrical installations. Part 4-41: Protection for safety - Protection against electric shock
NP 099 Normative for electrical equipment in explosive atmospheres. (ID 17 revision)
NP-I7-02 Normative for design and execution of electrical installation with
voltage up to 1000 V AC and 1500
According to EN 60204-1, the equipment shall be manufactured to correct operates, between of specified voltage.
According to HD 472 S1, under normal system condition the voltage at the supply terminals should not differ from the nominal voltage by more than
Voltage sensitive equipment, as like as capacitors for power factor corrections or electronic devices, which are intended to use at 500V, in the step down transformer neighborhood, it's strongly recommended to be ranged at 550V-600V.
Frequency in National Electric System is 50 Hz according to standard for distribution.
The voltage shall be specified by qualified persons, after documentation on site.
Main existent voltages are presented in table no. 1 and table no. 2
Table no. 1 Existent Low Voltage
Voltage Level (V) |
Earthing System |
Typical use / existent |
Advantage |
Disadvantage |
Remarks |
|||||
Distribution |
Well pump driver |
Lighting, automation & domestic appliances |
Gas compressor driver |
Water injection pump driver |
Oil pump driver |
|||||
TT |
Yes |
Yes |
Yes |
Standardized voltage Equipment available on the market Protections are safe, reliable and available on the market. The short-circuits -single or two/three phases are fast eliminate |
Comparing with IT system the continuity in supply is worst: A single phase short-circuit shut down the defective circuit |
Shall be considered for the new and modernized locations but no for wells |
||||
IT |
Offshore |
Offshore |
Single phase Earth leakage does not shut down the system. > Increase continuity of supply. |
Need continuous surveillance and procedures to detect the single earth leakage Protection are expensive and not reliable |
Recommended for process which require continuity of supply. |
|||||
IT |
Offshore |
Single phase Earth leakage does not shut down the system. > Increase continuity of supply. |
Need continuous surveillance and procedures to detect the single earth leakage Protection are expensive and not reliable |
Recommended for process which require continuity of supply. |
||||||
IT |
Yes |
Yes |
Yes |
Yes |
Single phase Earth leakage does not shut down the system. Increase continuity of supply. Comparing with 400 V system the level of loses are reduced (36%). |
No standardized voltage. Procurement issue, Complexes technical specifications Few offers. Need continuous surveillance and procedures to detect the single earth leakage Protection are expensive and not reliable Working with single phase leakage, in order to keep the continuity, over voltage the "healthy" phases. |
Recommended for process which require continuity of supply. Recommended for Electric Overhead Lines because is cheaper (3 wire instead of 4 at TT system) and ensure better continuity. |
|||
IT |
Yes |
As above-mentioned. |
As above Equipment is expensive and large Many issues with spare parts procurement. |
Used in Boldesti area. Is not recommended. Shall be replaced with 500 V when an opportunity appears or by developing a special project. |
Table no. 2 Existent Medium Voltages
Voltage Level (kV) |
Earthing System |
Typical use / status |
Advantage |
Disadvantage |
Remarks |
|||||
Distribution |
Well pump driver |
Lighting, automation & domestic appliances |
Gas compressor driver |
Water injection pump driver |
Oil pump driver |
|||||
IT |
Yes |
Yes |
Yes |
Yes |
Drivers: The loses in cable and motors
are lower than |
Expensive |
Recommended for drivers larger than kVA and distribution where it's already used: Suplac, Moinesti and Ticleni, constrained by local network. |
|||
IT |
Yes |
No standardized voltage. |
Not recommended for further appliance. It's used in Zemes area, Bolatau station cause of local constraints. |
|||||||
IT |
Yes |
Generally used for distribution. The network belongs to local Supplier. Some branches belong to PETROM |
The voltages from table no. 3 are recommended:
Table no. 3 Recommended Voltages for New Projects
Voltage Level (V) |
Earthing System |
Typical use |
Additional requirement |
|||||
Distribution |
Well pump driver |
Lighting, automation & domestic appliances |
Gas compressor driver |
Water injection pump driver |
Oil pump driver |
|||
TT |
Yes |
Yes |
Yes |
Control of residual current (RCD) between N and PE conductors |
||||
TN-S |
Yes |
Yes |
Yes |
Control of residual current (RCD) |
||||
IT |
Yes - Offshore |
Yes - Offshore |
Permanent insulation monitoring |
|||||
IT |
Yes - Offshore |
Permanent insulation monitoring |
||||||
IT |
Yes |
Yes |
Yes |
Yes |
Permanent insulation monitoring |
|||
6000V (6kV) |
IT |
Yes |
Yes |
Yes |
Yes |
Permanent insulation monitoring |
*) Phase to phase;
**) Phase to Earth / Neutral
IT -insulated neutral (high impedance) / unearthed;
TT - neutral point (
Well pumps driver
Gas compressors motors drive;
Oil & water pumps in park.
The circuit is simple and cheaper using only 3 wires.
Reduced loses trough voltage (500V comparing to 400V)
Figure 1 shows a typical recommended 500 V, IT diagram
Figure 1
The basic feature of the IT system of earthing is that, in the event of a short-circuit to earth fault, the system can continue to operate without interruption. Such a fault is referred to as a "first fault".
In this system, all exposed conductive parts of an installation are connected via PE conductors to an earth electrode at the installation, while the neutral point of the supply transformer is either isolated from earth or connected to earth through a high resistance (commonly 1,000 ohms or more) at 50 Hz
This means that the current through an earth fault will be measured in milli-amps, which will not cause serious damage at the fault position, or give rise to dangerous touch voltages, or present a fire hazard. The system may therefore be allowed to operate normally until it is convenient to isolate the faulty section for repair work.
This enhances continuity of service
In practice, the system earthing requires certain specific measures for its satisfactory exploitation:
The second fault results in a short- circuit through the earth and/or through PE bonding conductors.
This voltage is the most used throughout PETROM E&P to supply wells, parks and tanks farm: thousand transformer points, kilometer of OHL and thousand motors.
Many transformers, generic called as MT/0, 5 kV, have in fact the secondary voltage level at 525 V. In addition considering the behavior of Distribution Companies to work up to +10% over the MT nominal voltage results in a LV range at 550-600V which cause serious damage, especially to sensitive equipment as like as capacitors or electronics.
Some solution to avoid over voltage:
It is not allowed, for any reason, to buy equipment having nominal voltage lower than 500V, e.g. 400V, 440V or 480V.
Such equipment will be accepted only for testing purpose.
Final decision shall take into consideration the rise of cost and the decrease of efficiency caused by additional devices, e.g. transformers, but also the additional maintenance expenses. This decision shall be subject of written approval by Engineering Electrical Technical Authority
Existent Plants. Permanently Manned Facility.
IMD is mandatory and shall signal, acoustic and visual, the single phase fault.
Allowable operation time, with a single phase fault shall not exceed 6 (six) hours if is not otherwise specified by plant designer.
Existent Plants. Unmanned Facility.
IMD is mandatory and shall signal local the single phase fault.
Inspection / Operation Teams shall check the signal and report according to maintenance procedure [on hold
Fault localization and elimination shall not exceed 10 (ten) hours if is not otherwise specified by plant designer.
New Permanently Manned Plants.
IMD is mandatory and shall signal, acoustic and visual, the single phase fault.
Trip and remote communication are recommended.
Allowable operation time, with a single phase fault shall be specified by plant designer, according to maintenance procedure [on hold
New Unmanned Plants.
IMD is mandatory and shall signal local the single phase fault.
Remote communication is strongly recommended.
Allowable operation time, with a single phase fault shall be specified by plant designer, according to maintenance procedure [on hold
Figure 2 shows a typical recommended 400 V, TN-S system
Figure 2
Industrial appliance. Facilities: Parks, Tank Farms, Gas Compressor Stations, Water Injection Stations.
Figure 3 shows a typical recommended 400 V, TT system
RA x IDn ≤ 50V
RA and ID are defined and calculated as per standard HD 60364-4-41
Figure 3
Offshore
Figure 4 and 5 shows a typical recommended 400 V / 230 V, IT systems
Figure 4
Figure 5
Motors drive larger than 160kW, gas& air compressors and water injection pumps.
Figure 6 shows a typical recommended 6 kV, IT system
Figure 6
Politica de confidentialitate |
.com | Copyright ©
2024 - Toate drepturile rezervate. Toate documentele au caracter informativ cu scop educational. |
Personaje din literatura |
Baltagul – caracterizarea personajelor |
Caracterizare Alexandru Lapusneanul |
Caracterizarea lui Gavilescu |
Caracterizarea personajelor negative din basmul |
Tehnica si mecanica |
Cuplaje - definitii. notatii. exemple. repere istorice. |
Actionare macara |
Reprezentarea si cotarea filetelor |
Geografie |
Turismul pe terra |
Vulcanii Și mediul |
Padurile pe terra si industrializarea lemnului |
Termeni si conditii |
Contact |
Creeaza si tu |